unispa > Web interface > Processes > Events > Out on when

Out on when

The Out on when option is specific to Deadband and determines the side of the Deadband on which the input value must appear to switch the Output ON. Conversely, when the input value appears on the opposite side of the Deadband, the Output is automatically switched OFF.

If Below (false) is selected, the Output is turned ON when the input falls below the Deadband's Lower bound and turned OFF when the input rises above the Deadband's Upper bound, and vice-versa (true).

Deadband (standard) with Out on when option Below selected.
Deadband (standard) with Out on when option Above selected.

HTTP

The device will accept HTTP requests at the following URLs related to:

(POST) http://[IPv4]/var_set?param=evntopt_[PROCESS ID]&val=[VALUE]



POST: http://192.168.1.255/var_set?param=evntopt_12&val=1

will change the thermostat on Process #12 from active heating to active cooling.

Learn more in HTTP API.

MQTT

This parameter cannot be accessed via MQTT. Learn more in MQTT API.